In stock
Free Standard shipping
Typically arrives in 4 business days
- Output: 1000VA / 1000W
- Input: 100-125 VAC (Range: 70-155 VAC)
- 8 x NEMA 5-15R Total Outlets
Key specs
- Emergency Power Off (EPO) Support
- Yes
- Input Frequency
- 50/60 Hz ± 10 Hz
- Output Frequency
- 50/60 Hz ± 1%
- Rackmount Size
- 2 U
- Dimensions (W x H x D)
- 17.1 x 3.4 x 16.2" / 434 x 86 x 411 mm
- Weight
- 50.1 lb / 22.7 kg
Overview
This UPS offers runtimes measuring 7 minutes at full load, or 19.5 minutes at half load, while the backup battery has a 3-hour recharge time. The sine wave power output results in low total harmonic distortion and electrical noise for improved line clarity. In addition to an RJ45 port for cloud monitoring, the rear panel also incorporates a USB-B, serial, and EPO ports for communication purposes. The multifunction LCD screen rotates 90° and can be used to monitor battery and power conditions and alerts to potential problems. Use PowerPanel Personal software to control your UPS via a convenient dashboard interface. The PR1000RT2UC utilizes a 10' power cable with a NEMA 5-15P plug for flexible deployment.
Typical Applications
- Corporate Servers
- Department Servers
- Network Devices
- Storage Devices
- Telecom Installations
- VoIP Installations
Battery Backup
Supplies power long enough for equipment to properly shut down when utility power fails. Helps prevent loss of data and minimizes the component stress caused by a hard shutdown.Surge Protection
Diverts excess voltage away from sensitive electronic equipment during an AC power surge or power spike to prevent damage.Sine Wave Output
The UPS generates energy that is identical to, or cleaner than the utility company's power grid. Benefits include low total harmonic distortion, minimal electrical noise, and optimal line clarity.Automatic Voltage Regulation (AVR)
AVR increases or decreases the AC power and maintains a safe voltage level without switching to battery mode and conserving battery life.Battery Equalization Technology
Battery Equalization is an advanced charging process that maintains the voltages of the batteries at the same level to increase battery life.Critical Load Outlet
Extend runtimes for critical devices by powering down non-critical equipment to free up battery capacity.Fast Charge Technology
Allows UPS batteries to return to full capacity more rapidly by using a built-in charger inside of each UPS or EBM.Rotatable Multifunction LCD Panel
Tilts to provide a better viewing angle when the Smart App Sinewave is mounted low. Rotates 90° when placed in a tower format for horizontal viewing. Provides information on 47 different settings that include UPS status, UPS setup and control management, and testing options.Toolless Battery Panel Access
Makes battery replacement fast and simple. The faceplate features side latches for easy removal, and captive screws can be loosened by hand to open the battery cover.Rack/Tower Versatility
Allows for horizontal rack or vertical tower installation.RMCARD205 Network Management Card
This model accepts the RMCARD205 network management card for remote management and control via a standard web browser or network management system. Built-in cloud monitoring is included.PowerPanel Business Software
Provides IT professionals with tools for monitoring and managing the UPS and backup power. This software offers remote management functionality. Free software download available. See the Resources tab.Line-Interactive Topology
Exists when a line-interactive UPS has an autotransformer that regulates low voltages (e.g., brownouts) and over voltages (e.g., spikes) without having to switch to battery.ENERGY STAR
This model is an ENERGY STAR certified Uninterruptible Power Supply (UPS) system. ENERGY STAR is the trusted, government-backed symbol for energy-efficient products and practices that help save money and protect the environment.GreenPower UPS Bypass Design
A patented design that allows utility power to bypass the UPS transformer, when AC power is stable, which reduces energy consumption, noise, and heat buildup.Limited Three-Year Warranty
CyberPower will repair or replace a defective UPS system (including batteries) within three years of the purchase date.Connected Equipment Guarantee
CyberPower will repair or replace up to $400,000 of properly connected equipment if it is damaged by a power surge.Specifications
7 groups · 40 specs
- Total Outlets
- 8x NEMA 5-15R
- Plug Type
- NEMA 5-15P Offset Right-Angle
- Surge Protection
- Yes: 2430 Joules
- Maximum Wattage
- 1000 W
- Full-Load Runtime
- 7 Minutes
- Total Outlets
- 8x NEMA 5-15R
- Plug Type
- NEMA 5-15P Offset Right-Angle
- Surge Protection
- Yes: 2430 Joules
- Maximum Wattage
- 1000 W
- Full-Load Runtime
- 7 Minutes
- Total Outlets
- 8x NEMA 5-15R
- Protected Outlets
- 8x NEMA 5-15R (Battery and Surge)
- Plug Type
- NEMA 5-15P Offset Right-Angle
- USB Charging Ports
- No
- SmartSlot Interface
- No
- Coax Protection
- No
- Data Line Protection
- No
- Communications I/O
- USB via USB-B Serial via DE-9/DB-9 Ethernet (Unspecified) via RJ45
- Emergency Power Off (EPO) Support
- Yes
- Surge Protection
- Yes: 2430 Joules
- Maximum Wattage
- 1000 W
- Input Voltage Range
- 75 to 149 VAC
- Input Voltage Adjustable Range
- 70 to 155 VAC
- Input Frequency
- 50/60 Hz ± 10 Hz
- Output Voltage Range
- 100 to 125 VAC
- Output Frequency
- 50/60 Hz ± 1%
- Load Capacity
- 1000 VA
- Battery Capacity
- (7 VaH)
- Chemistry
- Lead-Acid
- Full-Load Runtime
- 7 Minutes
- Half-Load Runtime
- 19.5 Minutes
- Recharge Time
- 3 Hours
- User Replaceable
- Yes
- Replacement Battery
- RB1270X4H
- Operating Conditions
- 32 to 104°F / 0 to 40°C up to 95% Humidity
- Noise Level
- 52.5 dBA
- Certifications
- CSA, DOE, FCC, RoHS, UL, VCCI
- Cable Length
- 10' / 3 m
- Material of Construction
- Metal
- Rackmount Size
- 2 U
- Dimensions (W x H x D)
- 17.1 x 3.4 x 16.2" / 434 x 86 x 411 mm
- Weight
- 50.1 lb / 22.7 kg
- Box Dimensions (LxWxH)
- 21.5 x 21 x 10.5"
- Package Weight
- 58 lb
- Warranty
- Available